مهمترین آلارم هایی که در کنترل بویلر مشاهده میشوند در زیر آمده است.
Action | Audible and visual | Function |
| Alarm | Low water level | |
| Burner stop | Alarm | Low Low water level * |
| Alarm | High water level | |
| Feedwater pump stop | Alarm | High High water level |
| Alarm (overridden on slave boiler?) | Low steam pressure | |
| Burner stop | Alarm | High steam pressure |
| Stand-by pump start | Alarm | Low feedwater pressure |
| Stand-by pump start | Alarm | Low fuel oil pressure |
| Alarm | Low fuel oil temperature | |
| Alarm | High fuel oil temperature | |
| Burner stop | Alarm | Low combustion air pressure |
| Burner stop | Alarm | Low atomizing steam pressure |
| Burner stop | Alarm (overridden during light-up) | Flame failure ** |
| Burner stop | Alarm | Burner not in firing position |